9. Method for Calculating Other Primary Energy Consumption¶
This chapter shows the logic for calculating primary energy consumptions of other.
| Variable name | Description | Unit | Reference |
|---|---|---|---|
\(ROOMTYPE_{M,r}\) |
Building and room uses of room r to be calculated |
- |
Form 1: ① Building and room uses |
\(A_{M,r}\) |
Floor area of room r to be calculated |
m2 |
Form 1: ① Room Area |
\(n_{M}\) |
Number of rooms to be calculated |
- |
Form 1: ① Number of total rows for inputting room names |
| Variable Name | Description | Unit | References |
|---|---|---|---|
\(E_{M}\) |
Other primary energy consumption |
MJ/year |
Calculate a primary energy consumption of other from the following formula.
A coefficient \(a_{M,r}\,[\mathrm{MJ}/(\mathrm{m}^2\cdot\mathrm{year})]\) is a value specified in Appended Table 2 of MLIT’s 2016 Notification No. 265, representing other primary energy consumption per floor area.
This coefficient is specified for each room use. Based on Form 1: ① Building and room uses ( \(\mathrm{tem}\,[\mathrm{ROOMTYPE}_{M,r}]\) ) concerning room r to be calculated., an applicable coefficient \(a_{M,r}\) is extracted from Appended Table 2 of MLIT’s 2016 Notification No. 265.
Σ in the formula means the accumulation of primary energy consumptions of all rooms to be calculated in the input sheet. Specifically,the primary energy consumptions of all rooms inputted into “Form 1 Room specifications input sheet” are accumulated.
Where, the coefficient \(a_{M,r}\) is an accumulated annual value of equipment heat generation under the standard room use conditions in each room use that is converted into primary energy. A formula for calculating the value is shown below.
\(Q_{app,r,d,t}\) in the formula is the equipment heat generation at time \(t\) on date \(d\) [\(\mathrm{W/m^2}\)], specified for each room use under the standard room-use conditions.
A equipment heat generation during non-operation hours of air conditioning is expected in some room uses on the assumption of standby energy, but calculation of other energy consumption shall also cover the equipment heat generation during the non-operation hours.
Under the standard room use conditions, an equipment heat generation is always 0 in a room use for non-operation of air conditioning (room use whose standard value for air conditioning equipment is not set), so the coefficient \(\mathrm{tem}\,[a_{M,r}]\) is 0 in the room use for non-operation.