2.8 Design Primary Energy Consumption¶
The design primary energy consumption of air conditioning equipment is calculated by the following formula. If evaluating an air handling unit group without a secondary pump, the calculation is performed assuming that a virtual secondary pump (no control over the number of devices, temperature difference 0, rated flow rate 0, rated power consumption 0, rated flow rate control method) is installed between the air handling unit group and the heat source group.
| Variable Name | Description | Unit | Reference |
|---|---|---|---|
\(E_{AC,ahu,i}\) |
Annual primary energy consumption of the air handling unit group |
MJ/year |
2.5.12 |
\(E_{AC,pump,i}\) |
Annual primary energy consumption of the secondary pump group |
MJ/year |
2.6.10 |
\(E_{AC,ref,i}\) |
Annual primary energy consumption of the heat source group |
MJ/year |
2.7.18 |
| Variable Name | Description | Unit | Reference |
|---|---|---|---|
\(E_{AC}\) |
Annual primary energy consumption of air conditioning equipment |
MJ/year |
- |